DJ-A96T - Three-phase digital panel ammeter
The DJ-A96T three-phase digital ammeter is designed for accurate current monitoring in three-phase systems. It can display the instantaneous load on each phase L1, L2, L3 using external current transformers (CT). The device offers a clear display, easy setup, and reliable operation.
Main features
-
Current measurement in three-phase systems
-
Separate reading for phases L1, L2, L3
-
Measurement with external current transformers
-
Easy adjustment of CT ratio
-
Large and readable display - 3×4 digits, height 14 mm
-
Compact panel design
Technical parameters of the ammeter
-
Supply voltage: 230 V AC
-
Device consumption: < 4 VA
-
Current measurement range: 0.1...5.5 A
-
Supported CT range: 5/5 A to 5000/5 A
-
Measurement accuracy: ±2%
-
Display: LED, 3×4 digits, height 14 mm
-
Dimensions: 97,2 × 97,2 mm
-
Cutout dimensions: 91 × 91 mm
-
Depth: 45 mm
-
Package does not include current transformers (can be purchased separately)
Operating principle and settings
-
Connect the device according to the wiring diagram.
-
Connect the current transformers according to the expected current in the system (conversion xxxx/5 A).
-
Connect the CT wires to the terminals "kx" and "lx". The CT output must not exceed 5 A.
-
After turning on the power, press and hold the "Menu" button for 2 seconds.
-
Use the Up/Down buttons to set the conversion of the CTs used.
-
Save the settings by pressing and holding the "Menu" button.
-
When the load is connected, the ammeter starts measuring and displaying the current.
Note: Current transformers must always be grounded for safety reasons.
Technical characteristics of the solid-state output relay
(This time the listed parameters match the SSR - if it needs to be separate, I can split it).
-
Relay type: solid-state
-
Control voltage (input): 3...32 V DC
-
Switching voltage: 24...480 V AC (not suitable for motors)
-
Voltage drop when switching: < 3 V
-
Switching current: 5 mA
-
Coil voltage: 3...32 V DC
-
Maximum switching current: 25 A
-
Insulation strength: 2500 V AC
-
Switching method: switch on when current passes zero crossing
Online payment by card – after completing the order, you will be redirected to the payment page. The payment confirmation will be sent to your e‑mail.
Cash on delivery (COD) – you pay the amount directly to the driver upon delivery.
By bank transfer – at the latest on the next working day, you will receive a pro-forma invoice by e‑mail with the account number to which you can pay.
On invoice – this payment option is available for partners who have concluded a framework agreement with our company.
If you want to use one of the last two payment methods, please contact our business manager. He will explain to you how to receive an invoice with or without VAT.
The electrical equipment we supply meets high quality standards, has a 24-month warranty, and fully complies with all EU requirements.
In case of a complaint, no return costs will be charged.